Experimental investigation of mixed and forced convection generated by displacement ventilation with radiant wall heating

dc.authoridDalkilic, Ahmet Selim/0000-0002-5743-3937
dc.authoridAcikgoz, Ozgen/0000-0002-0095-829X
dc.authoridKarakoyun, Yakup/0000-0003-1868-452X
dc.authoridCamci, Muhammet/0000-0003-4283-1307
dc.contributor.authorCamci, Muhammet
dc.contributor.authorKarakoyun, Yakup
dc.contributor.authorAcikgoz, Ozgen
dc.contributor.authorDalkilic, Ahmet Selim
dc.date.accessioned2024-12-24T19:27:13Z
dc.date.available2024-12-24T19:27:13Z
dc.date.issued2022
dc.departmentSiirt Üniversitesi
dc.description.abstractThere is a rising necessity concerning low energy consumption and thermal comfort, thus, new systems combining displacement ventilation and radiant heating are becoming common as a research topic. The current paper covers free, mixed, and forced convection in an experimental chamber consisting of a radiant wall heating system and a baseboard level diffuser. Air temperature in the test room is adjusted using an air blower via a novel designed baseboard level slot diffuser along with a hydronic wall heating circuit. Simultaneously; an upward direction air jet is blown through the heated or the opposite wall under two scenarios. The ranges of air inlet velocity and temperature are selected to be between 0.25 and 12.5 m/s and 14-26 degrees C, correspondingly. The heat transfer characteristics pertaining to the heated wall are studied with respect to the influences of wall and air temperatures, air inlet velocities, and the location of the diffuser. To derive convective heat transfer coefficient correlations valid for mixed and forced types for a radiant heated wall, acquired data have been processed. The convective, radiative, and total heat transfer coefficient intervals of 3-14.1, 5.2-5.5, and 9.3-21.7 W/m2K have been obtained for the radiant heated wall coupled with airflows, correspondingly.
dc.description.sponsorshipYildiz Technical Uni-versity Scientific Research Projects Coordination Department; [FCD-2022-5092]
dc.description.sponsorshipAcknowledgement This study has been financially supported by Yildiz Technical Uni-versity Scientific Research Projects Coordination Department, Project ID: FCD-2022-5092.
dc.identifier.doi10.1016/j.icheatmasstransfer.2022.106476
dc.identifier.issn0735-1933
dc.identifier.issn1879-0178
dc.identifier.scopus2-s2.0-85140992356
dc.identifier.scopusqualityQ1
dc.identifier.urihttps://doi.org/10.1016/j.icheatmasstransfer.2022.106476
dc.identifier.urihttps://hdl.handle.net/20.500.12604/6535
dc.identifier.volume139
dc.identifier.wosWOS:000882460300002
dc.identifier.wosqualityQ1
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherPergamon-Elsevier Science Ltd
dc.relation.ispartofInternational Communications in Heat and Mass Transfer
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_20241222
dc.subjectConvective heat transfer coefficient
dc.subjectMixed convection
dc.subjectRadiant heated wall
dc.subjectDisplacement ventilation
dc.titleExperimental investigation of mixed and forced convection generated by displacement ventilation with radiant wall heating