Case studies on local mixed convection heat transfer coefficients along a radiant heated wall subjected to displacement ventilation

dc.authoridAcikgoz, Ozgen/0000-0002-0095-829X
dc.authoridDalkilic, Ahmet Selim/0000-0002-5743-3937
dc.authoridCamci, Muhammet/0000-0003-4283-1307
dc.authoridKarakoyun, Yakup/0000-0003-1868-452X
dc.contributor.authorCamci, Muhammet
dc.contributor.authorKarakoyun, Yakup
dc.contributor.authorAcikgoz, Ozgen
dc.contributor.authorDalkilic, Ahmet Selim
dc.date.accessioned2024-12-24T19:24:41Z
dc.date.available2024-12-24T19:24:41Z
dc.date.issued2023
dc.departmentSiirt Üniversitesi
dc.description.abstractAs the demand for energy-efficient air conditioning systems enabling thermal comfort criteria increases, the research into innovative systems that combine displacement ventilation and radiant heating is being more up-to-date. This work discusses local mixed convection heat transfer coefficients over a radiant heated wall in an experimental room coupled with displacement ventilation provided by a floor level nozzle. In the experimental chamber, the air enters the room either from the floor level of the analyzed heated wall as in scenario 1 or the opposite wall in scenario 2 in the upward direction. The intervals of air inlet temperature and velocity are set between 13-27 & DEG;C and 0-2.5 ms(-1), respectively. The obtained data have been analyzed from a physical point of view, and four correlations having R-sq. numbers of 0.93, 0.94, 0.94, and 0.98 have been developed for the local mixed convective heat transfer coefficients along a heated wall. The alterations of local convection heat transfer coefficients along an examined radiant heated wall affected by a slot diffuser delivering a lowest air inlet velocity of 0.5 ms(-1) and highest air inlet velocity of 2.5 ms(-1) are gained in the intervals of 2-5.8 Wm(-2) K-1 and 2.5-10 W m(-2) K-1, in turn.
dc.description.sponsorshipYTU Scientific Research Projects Coordination Department [FCD-2022-5092]
dc.description.sponsorshipAcknowledgementsThis study has been financially supported by YTU Scientific Research Projects Coordination Department, Project ID: FCD-2022-5092.
dc.identifier.doi10.1007/s10973-023-12262-6
dc.identifier.endpage7854
dc.identifier.issn1388-6150
dc.identifier.issn1588-2926
dc.identifier.issue15
dc.identifier.scopus2-s2.0-85159718886
dc.identifier.scopusqualityQ1
dc.identifier.startpage7845
dc.identifier.urihttps://doi.org/10.1007/s10973-023-12262-6
dc.identifier.urihttps://hdl.handle.net/20.500.12604/6098
dc.identifier.volume148
dc.identifier.wosWOS:001023269000022
dc.identifier.wosqualityQ2
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherSpringer
dc.relation.ispartofJournal of Thermal Analysis and Calorimetry
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_20241222
dc.subjectLocal convective heat transfer coefficient
dc.subjectMixed convection
dc.subjectRadiant heated wall
dc.subjectDisplacement ventilation
dc.subjectTemperature gradient
dc.titleCase studies on local mixed convection heat transfer coefficients along a radiant heated wall subjected to displacement ventilation